DONG Yu-jie, XU Dan, GUO Yi-du, YU Ying-ying. Research of Zone Interlocking Protection Scheme of Underground Power Grid and Its Real-time Performance[J]. Journal of Mine Automation, 2012, 38(11): 53-56.
Citation: DONG Yu-jie, XU Dan, GUO Yi-du, YU Ying-ying. Research of Zone Interlocking Protection Scheme of Underground Power Grid and Its Real-time Performance[J]. Journal of Mine Automation, 2012, 38(11): 53-56.

Research of Zone Interlocking Protection Scheme of Underground Power Grid and Its Real-time Performance

More Information
  • For the problem that communication network for power supply system of underground cannot meet real-time performance and reliability requirements of data transmission, and hardly achieves fast action and selectivity of protection simultaneously, the paper proposed a zone interlocking protection scheme based on switched Ethernet, and used OPNET network simulation software to study real-time performance of the switched Ethernet. The scheme adopts switched Ethernet of tree structure, and composes regional interlock system by adding smart interlock devices with Ethernet communication interface to integrated protection devices. The simulation results show that the maximum delay of overall network is less than 0.65 ms, the maximum end-to-end delay is less than 1 ms, and overall data transceiver flow is relatively smooth in the extreme case of 64 network nodes sending or receiving data at the same time, which illustrate that switched Ethernet has high stability and reliability to meet real-time requirements of interlock protection system in the region and prevent override trip accident.
  • Related Articles

    [1]YU Qun, CUI Guoliang, GU Feng, LIU Tao. Setting strategy of instantaneous current quick-breaking protection for mine power grid[J]. Journal of Mine Automation, 2023, 49(3): 107-114. DOI: 10.13272/j.issn.1671-251x.2022080092
    [2]LUAN Yongchun, CHEN Kunpeng. Analysis of anti-override trip program for underground power supply system[J]. Journal of Mine Automation, 2015, 41(9): 87-89. DOI: 10.13272/j.issn.1671-251x.2015.09.023
    [3]ZHAO Fu-yu. An Anti-Override Trip System Based on Principle of Zone Protectio[J]. Journal of Mine Automation, 2012, 38(11): 104-106.
    [4]HUANG Cui-bai, TANG Bai-shan. Design of an Improved Protection Scheme of Mine Zone Selective Interlocking[J]. Journal of Mine Automation, 2012, 38(11): 43-46.
    [5]LIU Jian-fu, LUO Rui-song. Application of Real-time Monitoring and Control System of Underground Power Supply in a Coal Mine[J]. Journal of Mine Automation, 2011, 37(8): 175-178.
    [6]CHEN Mei, YAO Qi-yun, LI Xin, CHEN Wei, LIU Zhen-ying. Research of Real-time Performance of Profibus-DP Single Master-station System[J]. Journal of Mine Automation, 2011, 37(1): 64-67.
    [7]ZHAO Xue-lei~(, 2), ZHANG Hong-bing~, ZHENG Zheng~, WANG Fu-zhong~. Design of Area-selected Interlocking Protection of Underground Power Supply System[J]. Journal of Mine Automation, 2010, 36(3): 48-50.
    [8]JIANG Xiu-zhu~, FENG Dong-qin~, XU Zhao~. Analysis of Real-time Performance of EPA and Its Calculatio[J]. Journal of Mine Automation, 2009, 35(4): 39-43.
    [9]WU Wen-xia, CHEN Bo-feng, GAO Ya. Research of Grade-skip Trip of Underground Power Grid and Its Suggestion of Resolutio[J]. Journal of Mine Automation, 2008, 34(6): 136-138.
    [10]LIU Ke. The Real-time Communication Technology of Industrial Ethernet and Its Headway[J]. Journal of Mine Automation, 2005, 31(3): 53-55.

Catalog

    Article Metrics

    Article views (50) PDF downloads (6) Cited by()
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return