YANG Yan, ZANG Qi-wei, YU Yang, et al. Grounding fault line selection method of power system of coal mine based on fuzzy theory[J]. Industry and Mine Automation, 2013, 39(3): 64-68.
Citation: YANG Yan, ZANG Qi-wei, YU Yang, et al. Grounding fault line selection method of power system of coal mine based on fuzzy theory[J]. Industry and Mine Automation, 2013, 39(3): 64-68.

Grounding fault line selection method of power system of coal mine based on fuzzy theory

  • Publish Date: 2013-03-10
  • For problem that fail selection often happened in single grounding fault line selection method, a new method combining zero sequence current power direction principle, wavelet transform analysis principle and gray relational analysis principle was proposed. The method uses the zero-sequence voltage multifractal spectrum to determine weights of the methods, and uses fuzzy inference theory for multi-criteria information fusion. Matlab simulation results show that the compound criterion which determines the weight through positioning method is suitable for single-phase grounding fault line selection in a variety of circumstances, and is not affected by system neutral grounding mode, run mode, out line number and grounding position, which achieves high accuracy single-phase grounding fault location.

     