ZHANG Guo-jun, SU Ke-jia. Line Selection Method of Selective Leakage Protection Based on Characteristic Quantity of Zero Sequence Current[J]. Industry and Mine Automation, 2012, 38(3): 51-54.
Citation: ZHANG Guo-jun, SU Ke-jia. Line Selection Method of Selective Leakage Protection Based on Characteristic Quantity of Zero Sequence Current[J]. Industry and Mine Automation, 2012, 38(3): 51-54.

Line Selection Method of Selective Leakage Protection Based on Characteristic Quantity of Zero Sequence Current

  • Publish Date: 2012-03-10
  • In allusion to the problem of low sensitivity and poor reliability of existing selective leakage protection device, the paper proposed a line selection method of selective leakage protection based on characteristic quantity of zero-sequence current. It analyzed logical relationship of zero-sequence current of each branch during failure of power supply system and introduced principle and realization of the method. The method creates characteristic quantities according to logical relationship and value relationship of secondary side zero-sequence current of zero-sequence current transformer of each branch, and takes the characteristic quantities as criterion of line selection. Matlab simulation result showed the method can effectively select the fault line.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (28) PDF downloads(4) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return