FAN Yi-long~, LI Hang~, YOU Guo-dong~. Design of Selective Leakage Protection Circuit Based on Method of Amplitude Discrimination and Phase Discriminatio[J]. Industry and Mine Automation, 2010, 36(7): 104-106.
Citation: FAN Yi-long~, LI Hang~, YOU Guo-dong~. Design of Selective Leakage Protection Circuit Based on Method of Amplitude Discrimination and Phase Discriminatio[J]. Industry and Mine Automation, 2010, 36(7): 104-106.

Design of Selective Leakage Protection Circuit Based on Method of Amplitude Discrimination and Phase Discriminatio

  • The paper proposed a design scheme of selective leakage protection circuit based on method of amplitude discrimination and phase discrimination for electrical control equipments of fully mechanized devices of coal mine underground.The selective leakage protection circuit applied the principle that the phase of zero-sequence current in fault line is in contrast to the one in non-fault line and the phase of zero-sequence current delays the phase of zero-sequence voltage in fault line.It realized function of selective leakage protection for electrical control equipments of fully mechanized devices of coal mine underground through comparison of phases of zero-sequence current and zero-sequence voltage as well as their amplitudes and the setted amplitude.The practice showed that the circuit has strong adaption ability,flexible application,and good reliability.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (42) PDF downloads(4) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return