ZHAO Jianwen, LI Ke, SUI Xiaona, et al. A new leakage protection method for mine power network[J]. Industry and Mine Automation, 2016, 42(2): 47-51. doi: 10.13272/j.issn.1671-251x.2016.02.012
Citation: ZHAO Jianwen, LI Ke, SUI Xiaona, et al. A new leakage protection method for mine power network[J]. Industry and Mine Automation, 2016, 42(2): 47-51. doi: 10.13272/j.issn.1671-251x.2016.02.012

A new leakage protection method for mine power network

doi: 10.13272/j.issn.1671-251x.2016.02.012
  • Publish Date: 2016-02-01
  • A new leakage protection method was proposed which was based on least-square matrix algorithm. In the method, zero sequence current signal of each brance is extracted on the basis of additional DC source system, and DC component of the zero sequence current signal is extracted by the least-square matrix algorithm. According to the DC component, insulation resistance value of each branch is calculated. If the insulation resistance value of a branch is bigger than action resistance value, the branch is judged as fault branch. The simulation result shows the method is accurate,reliable and with high adaptability.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (13) PDF downloads(5) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return